DC Cable Sizing Calculator – For PV

Current carrying capacity · cold Voc · voltage drop · cable loss · short-circuit check
Handy Tools
Engineering planning aid — verification required. Base current ratings, grouping factors and K constants in this tool originate from the supplied workbook and may include indicative values requiring confirmation against the current licensed Standards, manufacturer data and project conditions. The KEI PV array cable table below is intentionally limited to 6 mm² and 10 mm², matching the PV array cable sizes provided in this public tool. The table is not a substitute for project-specific derating. Do not use the result as a substitute for competent engineering design or statutory compliance review.

1. Project / Circuit

2. Electrical Inputs

V
A
V
A
no.
no.
%/°C
°C

3. Cable & Installation

mm²
m
A
Ω/km
This public PV array calculator intentionally provides only 6 mm² and 10 mm² conductor-size selections. Verify the applicable KEI current rating, installation method, correction factors and project requirements before relying on the result.

4. Correction Factors (CF)

°C
no.
factor
factor
The workbook's “Spaced ≥ 1D” grouping column is intentionally unpopulated pending verification. This web version therefore requires a verified grouping CF for that arrangement rather than treating a blank as zero.

6. Voltage Drop Inputs

%

7. Short-Circuit Inputs

kA
s
K is a verify-against-Table-5.1 input. It depends on conductor material and initial/final temperature conditions.

Calculated Design Summary

String Vmp
STC
Cold String Voc
max system voltage basis
Design Current
Imp × parallel
Overall
all applicable checks
Max conductor temp θc
INPUT BASIS
Temperature CF
CALC
Grouping CF
Extra mutual-heating CF
INPUT
Base rating Iz0
Corrected current capacity Iz
Utilisation
INFO
Minimum PV rating = 1.25 × Isc × parallel
Spare CCC above PV minimum
INFO

Voltage Drop & Loss

Calculated operating temperature θop
CALC
Temperature used for Vd
BASIS
R20
DATA
Resistance at design temperature
CALC
Voltage drop
CALC
Voltage drop % of String Vmp
Cable loss
INFO

Short-Circuit & Overall Result

Minimum conductor area Smin = I√t / K
VERIFY INPUTS
The overall verdict includes the thermal, PV current-rating, voltage-drop and short-circuit checks. This intentionally closes a gap in the supplied workbook's overall-result formula, which did not include its separate PV current-rating PASS/FAIL cell.

Reference / Verification Notes

AS/NZS 3008.1.1:2025: use the current licensed edition to verify installation method, base current rating, grouping/correction factors and K constant. The workbook identifies dedicated DC current-rating and voltage-drop provisions.
AS/NZS 5033:2021: verify PV maximum-current requirements, cable selection, voltage limits and protection for the actual array configuration. The workbook uses 1.25 × Isc × parallel as its PV cable current-rating check.
WA transition: WA Building and Energy advised full compliance with AS/NZS 3008.1.1:2025 from 19 June 2026. Users outside WA must verify the regulatory adoption applicable to their jurisdiction.
KEI H1Z2Z2-K PV Array Cable — Manufacturer Reference
SizeApprox. ODSingle cable in air @ 60°CSingle cable on surface @ 60°C2 loaded cables touching @ 60°CMax. R20Approx. weight
6 mm²6.5 mm70 A67 A57 A3.39 Ω/km87 kg/km
10 mm²7.4 mm98 A93 A79 A1.95 Ω/km132 kg/km
Source: KEI Industries, Solar DC Cable & Wire — BS EN 50618 H1Z2Z2-K product/rating table, accessed 9 September 2026. KEI manufacturer page. Manufacturer table values are reference data only; verify the exact cable construction, installation method, correction factors and project requirements before design use.

Mutual Heating Inputs

mm
mm
no.
no.
factor
factor

Thermal Interaction Result

Independence threshold
AIR BASIS
Actual spacing ÷ De
CALC
Bunches thermally independent?
Within-bunch grouping CF
Inter-bunch CF
Total grouping CF
INFO
For steady DC, this helper treats cable-to-cable interaction as a thermal grouping/spacing effect. It does not add an AC mutual-inductance loss term.
For buried groups, or close/critical spacing, use the applicable AS/NZS 3008 correction factors and project-specific thermal analysis. IEC 60287 may be required for rigorous thermal modelling.

Why the Helper Separates Thermal and Inductive Effects

Steady DC: current is constant, so there is no continuing induced voltage from mutual inductance between neighbouring circuits. Continuous interaction relevant to cable rating is therefore thermal.

AC or significant ripple: time-varying current can create proximity, eddy and sheath/armour losses. Those effects are outside this DC helper and require the appropriate AC/ripple cable-loss method.